Kingway - Model EADG250-EX2 - 250KVA Zone 2 Explosion Proof Diesel Generator for Hazardous Areas
From ZONE 2 Equipment
This 250KVA Zone 2 Hazardous Area Explosion Proof Diesel Generator is designed specifically for use in environments prone to explosions, such as coal mines, oil and gas fields, and petrochemical facilities. It is also suitable for applications in sectors like metallurgy, city gas, and chemical industries. The generator operates continuously at a power factor of 0.8 LAG. Built to meet Directive 2014/34/UE-ATEX and standards from the EN 60079, EN 1834, and EN 1755 series, it employs a Cummins NTAA855-G7 diesel engine with a displacement of 14L, governed at speeds of 1500/1800 rpm. The system is mounted in a DNV certified 2.7-1 skid frame and offers protection with IP55 rating. The generator's noise level is 85 dBA at 7 meters. It features a 24V electrical system, a battery rated at 210Ah, and supports 50Hz/60Hz frequency ranges. Designed to operate within an ambient temperature range of -25℃ to +60℃, and at altitudes up to 1000m.
-
Most popular related searches
Product Description:
Explosion-proof motors are mainly used in coal mines, oil and gas, petrochemical and chemical industries. In addition, it is also widely used in textile, metallurgy, city gas, transportation, grain and oil processing, papermaking, medicine and other departments. As the main power equipment, explosion-proof motors are usually used to drive pumps, fans, compressors and other transmission machinery.
There are many types of explosion-proof motors. In an explosion-hazardous area environment, to ensure safe production, the selection of explosion-proof motors is very important. When choosing an explosion-proof motor, you must understand its explosion-proof performance. Only when you choose an appropriate explosion-proof motor can you ensure the safety of use and not waste resources.
- Equipment: 250KVA Explosion-proof Diesel Engine Genset
- Directive : 2014/34/UE-ATEX
- Standard: EN 60079 series / EN 1834 series / EN 1755
- Convert to: Group II Equipment, Category 3G ( ZONE 2 IIB T3 Gc )
Specifications
- MODEL : EADG250-EX2
- COMPLETE MACHINE
- Explosion-proof Mark : #II 3G IIB T3 Gc
- Hazardous Zone : ZONE 2
- Certificate : 《Declaration of conformity》
- Typical generating set output (0.8 pf 25ºC) : 250KVA 400V /50HZ
- Max. Working Angle : 15°
- Noise Sound Level (±5 dBA at 7m) : 85
- Machine Weight (kg) : 3500 (dry)
- Dimensions: L x W x H mm : 4000X2200X2400
- Fuel tank : >300L
- DIESEL ENGINE
- Manufacturer : CUMMINS
- Model : NTAA855-G7
- Governed Speed (rpm) : 1500/1800
- Original Genset Prime Power (kW) : 250kW@1500rpm,275kW@1800rpm
- Displacement (L) : 14L
- No. of cylinders : 6
- Electrical System Voltage (V) : 24
- Rated Capacity of Battery : 210Ah
- GENERATORS
- Manufacturer : Kingway OEM
- Explosion-proof Mark : # II 3G Ex nA IIB T3 IP55
- Certificate number : 《Declaration of conformity》
- Hazardous Zone : ZONE 2
- Ambient temperature : -25℃~ +60℃
- Altitude : ≤1000M
- Rated Voltage : 400V
- Rated Frequency : 50HZ and 60HZ
- Rated REV : 1500RPM and 1800RPM
- Power Factor : 0.8 LAG
- Operation : Continuous (S1)
- IP Grade : IP55
- Controller : ComAp brand
Customer reviews
No reviews were found for Kingway - Model EADG250-EX2 - 250KVA Zone 2 Explosion Proof Diesel Generator for Hazardous Areas. Be the first to review!