Model 300 Series - Steam LP Boiler
From Commercial Boilers - Vertical Steam Boilers
The Series 300 Steam Boiler is available with firing inputs from 300,000 Btu/hr to 375,000 Btu/hr. However, many millions of Btu’s can be delivered by creating an efficient, fully modular system of multiple vessels properly sequenced by a control panel.
-
Most popular related searches
Design
Design
The Series 300 Steam Boiler is manufactured to exceed ASME Section IV standards and typically is used to provide operating pressure of up to 15 psi with nominal operating temperature of 218°F to 240°F. These vessels contain 37 vertical firetubes, each of which is 1½” diameter, each fitted with a high-efficiency turbulator for maximum heat transfer. The combustion chamber is fully water-backed, with burners that are UL listed. This boiler qualifies as a Category I gas appliance with industry standard controls wired to NEC specifications.
Safety
A well-made, heavy vessel is naturally a safer boiler. But Superior Boilers also have a firebox design that is completely backed by water, along with extra safety controls on the boiler that results in a very safe and secure package.
Standard Features
The following standard features include nationally known parts and controls that are available at most supply houses, allowing for quick and easy repair and maintenance, which can dramatically reduce down time:
- UL Listed Gas Trains and Control Systems.
- Choice of Power Burners.
- Main and Auxiliary Gas Valves
- Air Flow Switch
- Main Manual Leak Test Valve
- Pressure Control
- High-Limit With Manual Reset
- 5801-30 lb Pressure Gauge
- Siphon Loops
- 15 lb Pressure Relief Valve
- 150 Water Level Control
- Automatic Low Water Cutoff
- Gauge Glass Assembly
- Honeywell Aquastat Relay
- Burner Control Relay
- High Visibility Operating Light
- 1½” Diameter Firetubes of SA178-A Steel
- Turbulators for Maximum Heat Transfer
- Two Inches of Insulation With a Painted Steel Jacket.
Options
Superior Boiler offers several options to customize your boiler. A job is not complete until the boiler has been properly equipped for the application.
- Choice of burner manufacturers fired by natural gas, oil, propane, or dual fuel.
- Fan-Damper relays
- Barometric Dampers and Galvanized Tees
- Clean-out openings and plugs
- Microprocessor Control Panel for true lead-lag modulation
- Lifting Lugs
- Rail Legs
Customer reviews