Deep Sea Electronics Ltd (DSE)

Deep Sea Electronics Ltd (DSE)

Model DSE7450 - DC/Hybrid Generator Control Module

From

0

The DSE 7450 is a control module designed to control DC/Hybrid generators in supplying both a load and/or the charging of batteries.

Products Details

OVERALL SIZE

  • 240 mm x 172 mm x 57 mm (9.4” x 6.8” x 2.2”) 

PANEL CUTOUT SIZE

  • 220 mm x 160 mm (8.7' x 6.3')

MAXIMUM PANEL THICKNESS

  • 8.0 mm (0.3”)

WEIGHT

  • 0.92kg

PRODUCT VARIANTS

  • 7450-01 - 7450 DC Generator Control Module

Key Features

  • Automatic/manual start with configurable start/stop timers.
  • Configurable inputs/outputs (10/8).
  • Mains (Utility) failure detection.
  • AC/DC voltage measurement.
  • Battery temperature monitor/charge remaining display/depth of discharge display.
  • Backed-up real time clock.
  • Configurable event log (250).
  • Battery condition automatic start/stop.
  • USB, RS232, RS485, Ethernet and Modbus RTU/TCP communications.

Benefits

  • Offers flexibility to control the module manually, remotely or on pre-set timers and start/stop according to battery condition.
  • Provides multiple installation options.
  • Gives full mains (utility) back up.
  • Provides flexibility for use on AC or DC systems.
  • Provides information on battery temperature, charge remaining and depth of discharge.
  • Ensures data is not lost when module is disconnected from its power source.
  • Provides access to historical alarms and operational status.
  • Avoids the battery draining completely by starting the generator when the battery needs charging.
  • Provides secure and simple off site monitoring. All ports are continuously active.

Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING

  • 8 V to 35 V Continuous

CRANKING DROPOUTS

  • Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries

MAXIMUM OPERATING CURRENT

  • 260 mA at 12 V, 130 mA at 24 V

MAXIMUM STANDBY CURRENT

  • 120 mA at 12 V, 65 mA at 24 V

CHARGE FAIL/EXCITATION RANGE

  • 0 V to 35 V
OUTPUTS

OUTPUT A (FUEL)

  • 15 A DC at supply voltage

OUTPUT B (START)

  • 15 A DC at supply voltage

OUTPUTS C & D

  • 8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E,F,G,H,I & J

  • 2 A DC at supply voltage
GENERATOR

VOLTAGE RANGE

  • 15 V to 150 V AC (L-N)

FREQUENCY RANGE

  • 3.5 Hz to 75 Hz
  • MAINS (UTILITY)

VOLTAGE RANGE

  • 15 V to 333 V AC (L-N)

FREQUENCY RANGE

  • 3.5 Hz to 75 HzMAGNETIC PICK UP

VOLTAGE RANGE

  • +/- 0.5 V to 70 V

FREQUENCY RANGE

  • 10,000 Hz (max)

Environmental Testing Standards

ELECTRO-MAGNETIC  COMPATIBILITY

  • BS EN 61000-6-2
  • EMC Generic Immunity Standard for the Industrial Environment.
  • BS EN 61000-6-4
  • EMC Generic Emission Standard for the Industrial Environment.

ELECTRICAL SAFETY

  • BS EN 60950
  • Safety of Information Technology Equipment, including Electrical Business Equipment.

TEMPERATURE

  • BS EN 60068-2-1
  • Ab/Ae Cold Test -30°C.
  • BS EN 60068-2-2
  • Bb/Be Dry Heat +70°C.

VIBRATION

  • BS EN 60068-2-6
  • Ten sweeps in each of three major axes.
  • 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.

HUMIDITY

  • BS EN 60068-2-30
  • Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
  • BS EN 60068-2-78
  • Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

SHOCK

  • BS EN 60068-2-27
  • Three shocks in each of three major axes 15 gn in 11 ms.

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES

  • BS EN 60529
  • IP65 - Front of module when installed into the control panel with the optional sealing gasket.